Bus signal output module PG
The JB-111N is a component of the JABLOTRON system. It provides an output relay switch. It can be used for switching a door lock, blocking, signalling etc. The relay can be controlled with a programmable control panel (PG) output or according to the status of a section (set = relay on) or when there is an alarm in a chosen section (alarm = relay on). The device should be installed by a trained technician with a valid certificate issued by an authorized distributor.
Installation
When connecting the module to the system digital bus, always switch the power off. If the module is installed outside the protected area, the JA-110T bus insulator should be used for the external section of the wiring. The output contact does not contain an overload protection. |
The module can be installed into the JA-19xPL mounting box (by Jablotron) or into the control panel box. In order to comply with the security grade 2 classification, the module must be installed into the JA-194PL or JA-195PL mounting box together with the JA-111H TRB module.
- Use the switch (3) to set the required number of the PG output or the number of the section to which the relay should react – see the setting tables.
- Connect bus wires to the terminals (1).
- Switch on the system and test its functioning.
- Check the supply voltage at the bus terminals (red, black) when the relay is activated. The voltage must be at least 9 V.
- Connect the controlled device to the relay output terminals (5).
1 – digital bus terminals; 2 – red relay switching indicator; 3 – configuration switch; 4 – output relay; 5 – relay terminals;
Table 2: The relay reacts to arming the choosen section
Table 3: The relay reacts to an alarm in the choosen section
Enrolment to the system and settings
According to the type of control panel use recommended software or application – see control panel manual.
Technical specifications
Power | from control panel bus 12 V DC (9…15 V) |
---|---|
Quiescent current consumption | 5 mA/25 mA |
Maximal current consumption | 25 mA |
Relay contact rating: | |
Maximum switched voltage | 50 V AC/24 V DC |
Maximum switched current | 2 A |
Minimum switched current | 10 mA |
Dimensions | 78 x 40 x 15 mm |
Weight | 23 g |
Classification | Security grade 2/Environmental class II (according to EN 50131-1) Only when installed into the JA-194PL or JA-195PL mounting box together with the JA-111H TRB module |
Operational environment | indoor general |
Operational temperature range | -10 °C to +40 °C |
Average operational humidity | 75% RH, non-condensing |
Certification body | Trezor Test s.r.o. (no. 3025) |
Complies with | EN 50131-1, EN 50131-3, EN 50130-4, EN 55032, EN IEC 63000 |
JABLOTRON a.s. hereby declares that the product JB-111N is in a compliance with the relevant Union harmonisation legislation: Directives No: 2014/30/EU, 2011/65/EU. The original of the conformity assessment can be found at www.jablotron.com – Section Downloads. | ||
Note: Disposing of this product correctly will help save valuable resources and prevent any potential negative effects on human health and the environment, which could otherwise arise from inappropriate waste handling. Please return the product to the dealer or contact your local authority for further details of your nearest designated collection point. |