JA-120PC


If you want to save to PDF, please select
‘Save as PDF’ when the print dialog opens.

Bus PIR motion detector with a camera

switch to the manual for the JABLOTRON 100+ system

The JA-120PC is a component of the JABLOTRON system. It serves for the detection of human movement in building interiors and visual alarm confirmation. The camera takes colour photos with a resolution of up to 640 x 480 pixels. Taking photos is triggered by detecting human movement; this is so that the reason for the alarm is always recorded. The camera is equipped with a visible flash for taking photos in the dark. The images are saved in the internal memory of the detector and then they are forwarded to the control panel. And from the control panel they can be sent to MyJABLOTRON or ARC. The detector can also take a picture if it is required. The detector should be installed by a trained technician with a valid certificate issued by an authorised distributor.

Installation

When connecting the detector to the system bus, always switch the power off.
  1. Open the detector cover (by pushing the tab (4). Avoid touching the PIR sensor inside (14) – you could damage it.
  2. Take out the PCB – it is held by a tab (9).
  3. Punch through the holes for the screws and the cable in the plastic base. The recommended detector installation height is 2.5 m above the floor.
  4. Insert the bus cable (12) and attach the plastic base to the wall using screws (vertically, with the cover tab facing downwards).
  5. Re-insert the PCB and connect the bus cables to the terminals (11).
  6. Proceed according to the control panel installation manual.
   
Fig.1: Description of external and internal parts of the product
1 – flash for illumination; 2 – camera lens; 3 – PIR detector lens; 4 – cover tab; 5 – camera module; 6 – connecting cable; 7 – production code; 8 – red LED diode; 9 – PCB tab; 10 – yellow LED diode; 11 – bus terminals; 12 – bus cable; 13 – tamper contact; 14 – PIR sensor; 15 – Micro SD memory card; 16 – yellow LED diode of Micro SD card;

Assigment to the system

Depending on the type of control panel, use the recommended software or application, see the manual of the control panel.

Technical specifications

Powerfrom the control panel bus 12 V DC (9…15 V)
Quiescent current consumption5 mA
Maximal current consumption250 mA
Recommended installation height2.5 m above the floor
Detection angle/detection coverage55°/12 m (supplied lens)
Horizontal camera capture angle43 °
Range of the flashmax. 3 meters
Resolution of the cameraLQ 320*240; HQ 640*480 pixels
Photo size LQ/HQ (typically)2-10 kB/2-64 kB (6 kB/35 kB)
Typical (LQ) photo transmission time to the control panel20 s. (10 s)
Typical (LQ) photo transfer time to server15 s/GPRS; 2 s/LAN
Average operational humidity75% RH, without condensation
Dimensions, weight110 x 60 x 55 mm, 102 g
Operational temperature range-10 °C to +40 °C
Operational environmentIndoor general
Certification bodyTrezor Test s.r.o. (no. 3025)
ClassificationSecurity grade 2/Environmental class II. (According to EN 50131-1)
Complies withEN 50131-1, EN 50131-2-2, EN 50130-4, EN 55032, EN IEC 63000
Recommended screw2 x ø 3.5 x 40 mm (countersunk head)



JABLOTRON a.s. hereby declares that the JA-120PC is in compliance with the relevant European Union harmonisation legislation: Directives No: 2014/30/EU, 2011/65/EU, when used as intended. The original of the conformity assessment can be found at www.jablotron.com – the Downloads section.
Note: Disposing of this product correctly will help save valuable resources and prevent any potential negative effects on human health and the environment, which could otherwise arise from inappropriate waste handling. Please return the product to the dealer or contact your local authority for further details of your nearest designated collection point.

JA-120PCMMP52907