Bus external siren
Type: 1SIROUT2304LQ
Product is a component of the JABLOTRON system. It is used for system alarm indication outside a building. The siren should be installed by a trained technician with a valid certificate by authorized distributor.
Installation
- Push the bus cable through the hole (5) and secure it using prepared plastic tabs.
- Attach the siren to a suitable place using 2 screws through the hole (1). Use the integrated spirit level (7).
- Connect the bus cable to the terminals (10). If a back-up battery (3) is used, connect it to the connector (14).
- Put on the siren cover and attach it using locking screw (8). For easier handling of the cover, connect the string with the clip to the base.
cover type | colour and cover material | strobe colour |
---|---|---|
JA-1X2A-C-WH | white plastic | transparent |
JA-1X2A-C-GR | gray plastic | |
JA-1X2A-C-AN | anthracite plastic | |
JA-1X1A-C-ST | stainless-steel sheet | red |
JA-1X1A-C-ST-B | stainless-steel sheet | blue |
Note: The siren is also compatible with older types of cover JA-1X1A-C-XX-X.
1 – mounting holes; 2 – piezo sirens; 3 – back-up battery; 4 – reusable battery strap; 5 – hole for cable; 6 – PCB; 7 – spirit level; 8 – locking screw; 9 – string with clip for hanging the cover (can be disconnected by pressing the latch); 10 – bus terminals; 11 – serial number; 12 – tampers; 13 – LED indicator; 14 – back-up battery connector; 15 – yellow LED fault indicator; 16 – piezo siren connection (please note: high voltage);
Enrolment to the system and settings
Depending on the type of control panel, use the recommended software or application, see the control panel manual.
Please note: When selecting a stainless-steel cover, it is necessary to match the colour of the strobe and the light guide of the cover.
The siren can be installed without back-up battery, if sufficient system bus capacity allows. However, to comply with EN 50131-4, a back-up battery must be connected.
Technické parametry
Power | from the control panel bus 12 V (8–15 V) |
---|---|
Back-up battery | NiMH, type BAT-4V8-LH1800 / 4.8 V / 1800 mA (NiCd type BAT-4V8 / 4.8 V / 1800 mA can be connected also) Note: Back-up battery is not included, optional fitting |
Typical back-up battery lifetime | approx. 5 years |
Low back-up battery voltage | <4.6 V |
Quiescent current consumption from the bus | 2.5 mA |
Maximum current consumption from the bus | 450 mA |
Quiescent current consumption from the back-up battery | 3.6 mA |
Maximal current consumption from the back-up battery | 800 mA |
Type of warning device | type Z |
Piezo electric siren | 100 dB/m (new back-up battery) |
Dimensions (with cover) | 200 x 300 x 62 mm |
Weight (without back-up battery) | 413 g |
Classification | security grade 2/environmental class IV (according to EN 50131-1) |
Environment | outdoor general |
Operating temperature range | -25 °C to +60 °C |
Certification body | Trezor Test s.r.o. (no. 3025) |
Average operating humidity | 75% RH, non-condensation |
Complies with | EN 50130-4, EN 55032, EN IEC 62368-1, EN IEC 63000, EN 50131-1, -4, -6 |
Can be operated to | ERC REC 70-03 |
Recommended screw | 2 x |
JABLOTRON a.s. hereby declares that the 1SIROUT2304LQ is in a compliance with the relevant Union harmonisation legilation: Directives No.: 2014/35/EU, 2014/30/EU, 2011/65/EU, if it is used as intended. The original of the conformity assessment can be found at www.jablotron.com Section Downloads. | ||
Note: Disposing of this product correctly will help save valuable resources and prevent any potential negative effects on human health and the environment, which could otherwise arise from inappropriate waste handling. Please return the product to the dealer or contact your local authority for further details of your nearest designated collection point. |
JA-113A RB | MLQ54600 (27.02.2025) |
---|