Bus PIR motion detector
The JA-112P is a bus device of the JABLOTRON system. It is used to detect movement of persons in interiors of buildings. Its guaranteed detection coverage is 90° horizontally and detection range is 12 m. The detector should be installed by a trained technician with a valid certificate issued by an authorized distributor.
Installation
When connecting the detector to the bus, always switch the system power off. |
- Open the detector cover by pressing the cover tab (4). Avoid touching the PIR sensor inside (10) – you could damage it.
- Take out the PCB – it is held by a tab.
- Punch through the holes for the screws and the cable in the plastic base. The recommended installation height is 2.5 m above the floor.
- Insert the bus cable and attach the plastic base to the wall (vertically, with the cover tab facing downwards).
- Insert the PCB back and connect the bus cables to the terminals (6).
- The control panel must be in Service mode. Proceed by following the control panel installation manual.. When the device is switched on, the yellow LED (7) starts flashing to indicate that the module has not been enrolled into the system.
- Close the detector cover and secure it with a locking screw (3). Then test the detector’s function.
1 – LED indicator; 2 – PIR lens; 3 – hole for locking screw; 4 – cover tab; 5 – connector for external tamper contact of the JA-191PL; 6 – bus terminals; 7 – LED status indicators; 8 – production code; 9 – tamper sensor; 10 – PIR sensor;
Assigment to the system
Depending on the type of control panel, use the recommended software or application, see the manual of the control panel.
Technické parametry
Power | from the control panel bus 12 V DC (9–15 V) |
---|---|
Quiescent current consumption | 5 mA |
Maximal current consumption | 16 mA |
Recommended installation height | 2.5 m above the floor |
Detection angle/detection range | 90°/12 m |
Dimensions | 62 x 110 x 40 mm |
Weight | 77 g |
Classification | Grade 2/Environmental class II (According to EN 50131-1) |
Operational environment | Indoor general |
Operational temperature range | -10 °C to +40 °C |
Average operational immunity | 75% RH, non-condensing |
Certification body | Trezor Test s.r.o. (no. 3025), KIWA |
Complies with | EN 50131-1, EN 50131-2-2, EN 50130-4, EN 55032, EN IEC 63000, T 031 (comply by installation in the centre of the inner corner) |
Recommended screw | 2 x ø 3.5 x 40 mm (countersunk head) |
JABLOTRON ALARMS a.s. hereby declares that the JA-112P, JA-112P-GR, JA112P-AN are in compliance with the relevant European Union harmonisation legislation: Directives No: 2014/30/EU, 2011/65/EU, when used as intended. The original of the conformity assessment can be found at www.jablotron.com – the Downloads section. | ||
Note: Disposing of this product correctly will help save valuable resources and prevent any potential negative effects on human health and the environment, which could otherwise arise from inappropriate waste handling. Please return the product to the dealer or contact your local authority for further details of your nearest designated collection point. |
JA-112P | MMN57106 (23.10.2024) |
---|